Technical reference · English

Technical selection

VersionATK-B6LATK-B6L(H)
Current rating (A)6, 10, 16, 20, 25, 32, 40, 50, 636, 10, 16, 20, 25, 32, 40, 50, 63, 80
Poles1P+N, 2P, 3P, 3P+N, 4P1P+N, 2P, 3P, 3P+N, 4P
Ue (V)AC 230 / 400AC 230 / 400
Ui (V)—500
Uimp (kV)44
Icn (kA)610
IΔn (mA)30, 50, 75, 10030, 50, 75, 100
IΔno—0.5 IΔn
IΔm (A)—2000
Mechanical operations1000020000
Electrical operations40004000

Trip curves

CD
5–10 In10–15 In

Operating conditions

°CmDIN rail
−5 … +40≤ 200035 mm

Dimensions and installation

PolesATK-B6L 6–32 A (mm)ATK-B6L 40–63 A (mm)ATK-B6L(H) (mm)
1P+N18 + 2718 + 3654
2P36 + 2736 + 3672
3P54 + 3654 + 49103
3P+N54 + 4554 + 63117
4P72 + 4572 + 63135

Installation and accessories

Select accessories for the exact breaker version; standard and high-breaking-capacity models have different accessory mounting arrangements.