RCM53xA provides Type A residual-current monitoring for hospital circuits and driven equipment. Used with a separate zero-sequence current transformer, it observes leakage and stray-current changes. Switching outputs support circuit-monitoring arrangements. Confirm the transformer and interfaces for the actual circuit conditions.
Medical system applicationExplore power distribution for hospital Group 2 locationsExplore how isolation power, monitoring, alarms and critical loads work together.Explore technical detailsPRODUCT INSIGHTS
Works with a separate zero-sequence current transformer; check the compatible model in the selection table.
Monitor leakage and stray-current conditions in hospital and power circuits.
Provides switching outputs for integration with associated circuit-monitoring equipment.
Application conceptBUILT FOR YOUR ENVIRONMENT
TECHNICAL SPECIFICATIONS
Type A residual-current monitor for AC and pulsating DC residual currents, with a 15 Hz–2 kHz frequency range.
True-RMS measurement range: 0–30 A.
Selectable thresholds: 10, 30, 100, 300 or 500 mA, and 1, 3, 5, 10 or 30 A.
Dual-relay alarm outputs, with optional 4–20 mA analogue output.
Approximately 53 mm wide; 3-module DIN-rail mounting.