Technical reference · English

Frame and voltage selection

FrameInUeUiUimp
2000400 / 630 / 800 / 1000 / 1250 / 1600 / 2000 AAC 400 V · 690 V1000 V12 kV
2000H400 / 630 / 800 / 1000 / 1250 / 1600 / 2000 AAC 400 V · 690 V1000 V12 kV
3200HU2000 / 2500 / 3200 AAC 800 V · 1000 V · 1140 V1250 V12 kV
4000M1600 / 2000 / 2500 / 3200 / 3600 / 4000 AAC 400 V1000 V12 kV
4000H1600 / 2000 / 2500 / 3200 / 3600 / 4000 AAC 400 V · 690 V1000 V12 kV

Breaking capacity by model

FrameUeIcuIcsIcw
2000AC 400 V80 kA50 kA50 kA / 1s
2000AC 690 V50 kA50 kA50 kA / 1s
2000HAC 400 V80 kA65 kA65 kA / 1s
2000HAC 690 V65 kA50 kA50 kA / 1s
3200HUAC 800 V70 kA70 kA70 kA / 1s
3200HUAC 1000 V65 kA65 kA65 kA / 1s
3200HUAC 1140 V50 kA50 kA50 kA / 1s
4000MAC 400 V85 kA85 kA85 kA / 1s
4000HAC 400 V100 kA100 kA100 kA / 1s
4000HAC 690 V85 kA85 kA85 kA / 1s

Each rating belongs to its listed frame and voltage; the maximum values do not apply to every version.

Coordinate short-time delay with downstream fault clearing and the breaker's Icw. Transfer restoration and selective fault isolation are separate functions; neither guarantees uninterrupted power by itself.