Technical reference · English
Engineering design values
| Technical selection | Engineering design values |
|---|---|
| Nominal supply | 24 V DC |
| Channels | 6 |
| Recording duration | 100 ms |
| Records per device | 10 |
| Network capacity | 247 / 1,482 devices / channels |
| DIN rail | 35 mm |
| Main body | 252 × 64 mm |
| Sensor supply target | 5 V / 150 mA |
| Sensor input / zero-current level | 0–5 V / 2.5 V |
| Nominal DC / instantaneous peak | 60 mA DC / ±70 mA |
| Sensor frequency / attenuation point | DC–1000 Hz / 1 kHz: −3 dB |
| ADC acquisition / averaged output | 50 ksample/s / 12.5 ksample/s |
| Calculated maximum channel skew | 1.286 µs |
| Quantisation before averaging | 0.0366 mA/LSB |
| DC / AC RMS processing target | Hann: 200 ms / 20 ms |
| Storage / clock | 16 MB Flash / RTC |
| Ethernet | 10/100 Mbps |
| RS-485 | Modbus RTU / ≥115200 baud |
| CAN | CAN |
| USB | Type-C |
The specified network comprises up to 247 devices and 1,482 channels. Firmware, calibration and complete-device validation remain part of engineering completion.
The sensor supply target is 150 mA per channel. ADC design uses 50 ksample/s acquisition and four-point averaging to 12.5 ksample/s per channel. The 1.286 µs maximum skew and 0.0366 mA/LSB quantisation are calculated values, not measured accuracy. The proposed RMS calculation uses a 200 ms Hann window with 20 ms refresh. Body dimensions exclude projections.
The 60 mA nominal DC value and ±70 mA instantaneous limit require sensor validation. With zero DC offset, a ±70 mA sinusoidal peak is approximately 49.5 mA RMS; combined DC offset and AC peak must stay within the sensor range. The 1 kHz frequency limit is the sensor's −3 dB point. Full-system accuracy, temperature ratings, consumption and protection class require product tests.
Application concept